MCF8329HS-Q1 supports three different kinds of profiles (linear, step, forward-reverse) to convert the DUTY_CMD to the reference control signal. The input control reference signal can be motor speed, DC input power, motor current (iq), or motor voltage (modulation index control) as configured by CTRL_MODE. The different profiles can be configured through REF_PROFILE_CONFIG. When REF_PROFILE_CONFIG is set to 00b, the profiler is not applied and the input reference is same as the duty command as explained in Section 7.3.6.5.5.
In speed control mode, the profiler output REF_X corresponds to percentage of Maximum Speed (configured by MAX_SPEED) as shown in Equation 4. In power control mode, the profiler output REF_X corresponds to percentage of Maximum Power (configured by MAX_POWER) as shown in Equation 5. In the current control mode (iq control) the profiler output REF_X corresponds to the percentage of ILIMIT as shown in Equation 6. In voltage control mode (Modulation index control mode) REF_X corresponds to the percentage of Vd and Vq modulation index applied voltage to the motor as shown in Equation 7 .