SDAA451 July 2026 ADS131M08
Phase shift refers to the horizontal shift of a sinewave along the x-axis. Equation 1 specifies the standard sinewave equation centered around the origin with no phase shift:
Where:
Figure 2-1 shows this equation graphically as a single sinewave.
A phase shift can exist between two measured sinewave signals. This phase shift is denoted by and the equation for a sinewave with a phase shift is given by Equation 2:
Where:
Figure 2-2 shows two sinewaves plotted with a phase shift of φ between them.
As an example, a load phase angle can exist between the voltage and current waveforms of a power measurement system. This phase shift breaks into two distinct components:
Figure 2‑3 shows typical power measurement systems waveforms, with a green voltage signal V(t) and a red current signal I(t) :
The signals in Figure 2-3 can be expressed as:
Where:
Equation 4 shows that the load phase angle is subtracted from the angular frequency ωt – φ. This subtraction shifts I(t) to the right along the x-axis relative to V(t) as shown in Figure 2-3.This relationship is referred to as I(t) lagging V(t) and is common for an inductive load. The phase shift expressed as shifts leftward along the x-axis relative . This relationship is referred to as leading the and is common for a capacitive load. In a purely resistive load and the two waveforms are aligned. As the reactive component of the load increases, increases and the misalignment between the waveforms grows.
Equation 5 uses Equation 3 and Equation 4 to calculate instantaneous power - the power at any single point in time:
Equation 5 calculates the ideal instantaneous power with a phase shift resulting from only the load phase angle. As described earlier, however, phase error also contributes to the total phase shift. Equation 6 calculates the instantaneous power with a phase shift resulting from both the load phase angle and phase error:
Where:
Equation 6 provides a power value at a single point in time that will change as the voltage and current waveforms oscillate. Therefore, an actual power measurement system needs to average the instantaneous power over a complete cycle to determine the real power consumed by the load during operation. Averaging Equation 6 over a complete cycle yields the average real power formula shown in Equation 7:
A phase error, , remaining in the system without calibration introduces systematic error into the power measurement. Equation 8 calculates the resulting power measurement error due to the phase error:
For example, apply Equation 8 to a 50 Hz system with a 0.5 power factor (60° phase angle) to observe the impact of a 0.1° phase error on a power measurement.
A phase error of 0.1° produces a 0.3% measured power error compared to the real power. A phase error of 1° - common among class 1.0 CTs at a power factor of 0.5 -produces a 3% measured power error compared to the real power. Calibrating out the phase error is critical to ensuring accurate power measurements.