ZHCSOF7B september   2022  – june 2023 TPS25990

PRODUCTION DATA  

  1.   1
  2. 特性
  3. 应用
  4. 说明
  5. Revision History
  6. 说明(续)
  7. Pin Configuration and Functions
  8. Specifications
    1. 7.1  Absolute Maximum Ratings
    2. 7.2  ESD Ratings
    3. 7.3  Recommended Operating Conditions
    4. 7.4  Thermal Information
    5. 7.5  Electrical Characteristics
    6. 7.6  Logic Interface DC Characteristics
    7. 7.7  Telemetry
    8. 7.8  PMBus Interface Timing Characteristics
    9. 7.9  External EEPROM Interface Timing Characteristics
    10. 7.10 Timing Requirements
    11. 7.11 Switching Characteristics
    12. 7.12 Typical Characteristics
  9. Detailed Description
    1. 8.1 Overview
    2. 8.2 Functional Block Diagram
    3. 8.3 Feature Description
      1. 8.3.1  Undervoltage Protection
      2. 8.3.2  Insertion Delay
      3. 8.3.3  Overvoltage Protection
      4. 8.3.4  Inrush Current, Overcurrent, and Short-Circuit Protection
        1. 8.3.4.1 Slew rate (dVdt) and Inrush Current Control
          1. 8.3.4.1.1 Start-Up Timeout
        2. 8.3.4.2 Steady-State Overcurrent Protection (Circuit-Breaker)
        3. 8.3.4.3 Active Current Limiting During Start-Up
        4. 8.3.4.4 Short-Circuit Protection
      5. 8.3.5  Single Point Failure Mitigation
        1. 8.3.5.1 IMON Pin Single Point Failure
        2. 8.3.5.2 ILIM Pin Single Point Failure
        3. 8.3.5.3 IREF Pin Single Point Failure
      6. 8.3.6  Analog Load Current Monitor (IMON)
      7. 8.3.7  Overtemperature Protection
      8. 8.3.8  Analog Junction Temperature Monitor (TEMP)
      9. 8.3.9  FET Health Monitoring
      10. 8.3.10 General Purpose Digital Input/Output Pins
        1. 8.3.10.1 Fault Response and Indication (FLT)
        2. 8.3.10.2 Power Good Indication (PG)
        3. 8.3.10.3 Parallel Device Synchronization (SWEN)
      11. 8.3.11 Stacking Multiple eFuses for Unlimited Scalability
        1. 8.3.11.1 Current Balancing During Start-Up
      12. 8.3.12 General Purpose Comparators
      13. 8.3.13 Output Discharge
      14. 8.3.14 PMBus® Digital Interface
        1. 8.3.14.1  PMBus® Device Addressing
        2. 8.3.14.2  SMBus Protocol
        3. 8.3.14.3  SMBus™ Message Formats
        4. 8.3.14.4  Packet Error Checking
        5. 8.3.14.5  Group Commands
        6. 8.3.14.6  SMBus™ Alert Response Address (ARA)
        7. 8.3.14.7  PMBus® Commands
          1. 8.3.14.7.1 Detailed Descriptions of PMBus® Commands
            1. 8.3.14.7.1.1  OPERATION (01h, Read/Write Byte)
            2. 8.3.14.7.1.2  CLEAR_FAULTS (03h, Send Byte)
            3. 8.3.14.7.1.3  RESTORE_FACTORY_DEFAULTS (12h, Send Byte)
            4. 8.3.14.7.1.4  STORE_USER_ALL (15h, Send Byte)
            5. 8.3.14.7.1.5  RESTORE_USER_ALL (16h, Send Byte)
            6. 8.3.14.7.1.6  BB_ERASE (F5h, Send Byte)
            7. 8.3.14.7.1.7  FETCH_BB_EEPROM (F6h, Send Byte)
            8. 8.3.14.7.1.8  POWER_CYCLE (D9h, Send Byte)
            9. 8.3.14.7.1.9  MFR_WRITE_PROTECT (F8h, Read/Write Byte)
            10. 8.3.14.7.1.10 CAPABILITY (19h, Read Byte)
            11. 8.3.14.7.1.11 STATUS_BYTE (78h, Read Byte)
            12. 8.3.14.7.1.12 STATUS_WORD (79h, Read Word)
            13. 8.3.14.7.1.13 STATUS_OUT (7Ah, Read Byte)
            14. 8.3.14.7.1.14 STATUS_IOUT (7Bh, Read Byte)
            15. 8.3.14.7.1.15 STATUS_INPUT (7Ch, Read Byte)
            16. 8.3.14.7.1.16 STATUS_TEMP (7Dh, Read Byte)
            17. 8.3.14.7.1.17 STATUS_CML (7Eh, Read Byte)
            18. 8.3.14.7.1.18 STATUS_MFR_SPECIFIC (80h, Read Byte)
            19. 8.3.14.7.1.19 STATUS_MFR_SPECIFIC_2 (F3h, Read Word)
            20. 8.3.14.7.1.20 PMBUS_REVISION (98h, Read Byte)
            21. 8.3.14.7.1.21 MFR_ID (99h, Block Read)
            22. 8.3.14.7.1.22 MFR_MODEL (9Ah, Block Read)
            23. 8.3.14.7.1.23 MFR_REVISION (9Bh, Block Read)
            24. 8.3.14.7.1.24 READ_VIN (88h, Read Word)
            25. 8.3.14.7.1.25 READ_VOUT (8Bh, Read Word)
            26. 8.3.14.7.1.26 READ_IIN (89h, Read Word)
            27. 8.3.14.7.1.27 READ_TEMPERATURE_1 (8Dh, Read Word)
            28. 8.3.14.7.1.28 READ_VAUX (D0h, Read Word)
            29. 8.3.14.7.1.29 READ_PIN (97h, Read Word)
            30. 8.3.14.7.1.30 READ_EIN (86h, Block Read)
            31. 8.3.14.7.1.31 READ_VIN_AVG (DCh, Read Word)
            32. 8.3.14.7.1.32 READ_VIN_MIN (D1h, Read Word)
            33. 8.3.14.7.1.33 READ_VIN_PEAK (D2h, Read Word)
            34. 8.3.14.7.1.34 READ_VOUT_AVG (DDh, Read Word)
            35. 8.3.14.7.1.35 READ_VOUT_MIN (DAh, Read Word)
            36. 8.3.14.7.1.36 READ_IIN_AVG (DEh, Read Word)
            37. 8.3.14.7.1.37 READ_IIN_PEAK (D4h, Read Word)
            38. 8.3.14.7.1.38 READ_TEMP_AVG (D6h, Read Word)
            39. 8.3.14.7.1.39 READ_TEMP_PEAK (D7h, Read Word)
            40. 8.3.14.7.1.40 READ_PIN_AVG (DFh, Read Word)
            41. 8.3.14.7.1.41 READ_PIN_PEAK (D5h, Read Word)
            42. 8.3.14.7.1.42 READ_SAMPLE_BUF (D8h, Block Read)
            43. 8.3.14.7.1.43 READ_BB_RAM (FDh, Block Read)
            44. 8.3.14.7.1.44 READ_BB_EEPROM (F4h, Block Read)
            45. 8.3.14.7.1.45 BB_TIMER (FAh, Read Byte)
            46. 8.3.14.7.1.46 PMBUS_ADDR (FBh, Read/Write Byte)
            47. 8.3.14.7.1.47 VIN_UV_WARN (58h, Read/Write Word)
            48. 8.3.14.7.1.48 VIN_UV_FLT (59h, Read/Write Word)
            49. 8.3.14.7.1.49 VIN_OV_WARN (57h, Read/Write Word)
            50. 8.3.14.7.1.50 VIN_OV_FLT (55h, Read/Write Word)
            51. 8.3.14.7.1.51 VOUT_UV_WARN (43h, Read/Write Word)
            52. 8.3.14.7.1.52 VOUT_PGTH (5Fh, Read/Write Word)
            53. 8.3.14.7.1.53 OT_WARN (51h, Read/Write Word)
            54. 8.3.14.7.1.54 OT_FLT (4Fh, Read/Write Word)
            55. 8.3.14.7.1.55 PIN_OP_WARN (6Bh, Read/Write Word)
            56. 8.3.14.7.1.56 IIN_OC_WARN (5Dh, Read/Write Word)
            57. 8.3.14.7.1.57 VIREF (E0h, Read/Write Byte)
            58. 8.3.14.7.1.58 GPIO_CONFIG_12 (E1h, Read/Write Byte)
            59. 8.3.14.7.1.59 GPIO_CONFIG_34 (E2h, Read/Write Byte)
            60. 8.3.14.7.1.60 ALERT_MASK (DBh, Read/Write Word)
            61. 8.3.14.7.1.61 FAULT_MASK (E3h, Read/Write Word)
            62. 8.3.14.7.1.62 DEVICE_CONFIG (E4h, Read/Write Word)
            63. 8.3.14.7.1.63 BB_CONFIG (E5h, Read/Write Byte)
            64. 8.3.14.7.1.64 OC_TIMER (E6h, Read/Write Byte)
            65. 8.3.14.7.1.65 RETRY_CONFIG (E7h, Read/Write Byte)
            66. 8.3.14.7.1.66 ADC_CONFIG_1 (E8h, Read/Write Byte)
            67. 8.3.14.7.1.67 ADC_CONFIG_2 (E9h, Read/Write Byte)
            68. 8.3.14.7.1.68 PK_MIN_AVG (EAh, Read/Write Byte)
            69. 8.3.14.7.1.69 VCMPxREF (EBh, Read/Write Byte)
            70. 8.3.14.7.1.70 PSU_VOLTAGE (ECh, Read/Write Byte)
            71. 8.3.14.7.1.71 CABLE_DROP (EDh, Read/Write Byte)
            72. 8.3.14.7.1.72 GPDAC1 (F0h, Read/Write Byte)
            73. 8.3.14.7.1.73 GPDAC2 (F1h, Read/Write Byte)
            74. 8.3.14.7.1.74 INS_DLY (F9h, Read/Write Byte)
        8. 8.3.14.8  Analog-to-digital Converter
        9. 8.3.14.9  Digital-to-analog Converters
        10. 8.3.14.10 DIRECT format Conversion
        11. 8.3.14.11 Blackbox Fault Recording
    4. 8.4 Device Functional Modes
  10. Application and Implementation
    1. 9.1 Application Information
      1. 9.1.1 Single Device, Standalone Operation
      2. 9.1.2 Multiple Devices, Parallel Connection
      3. 9.1.3 Multiple Devices, Independent Operation (Multi-zone)
    2. 9.2 Typical Application: 12-V, 4-kW Power Path Protection with PMBus® Interface in Datacenter Servers
      1. 9.2.1 Design Requirements
      2. 9.2.2 Detailed Design Procedure
      3. 9.2.3 Application Performance Plots
    3. 9.3 Best Design Practices
    4. 9.4 Power Supply Recommendations
      1. 9.4.1 Transient Protection
      2. 9.4.2 Output Short-Circuit Measurements
    5. 9.5 Layout
      1. 9.5.1 Layout Guidelines
      2. 9.5.2 Layout Example
  11. 10Device and Documentation Support
    1. 10.1 Documentation Support
      1. 10.1.1 Related Documentation
    2. 10.2 接收文档更新通知
    3. 10.3 支持资源
    4. 10.4 Trademarks
    5. 10.5 静电放电警告
    6. 10.6 术语表
  12. 11Mechanical, Packaging, and Orderable Information

封装选项

机械数据 (封装 | 引脚)
散热焊盘机械数据 (封装 | 引脚)
订购信息
ADC_CONFIG_1 (E8h, Read/Write Byte)

ADC_CONFIG_1 is a manufacturer-specific command for configuring or reading channel selections and modes for ADC sampling as described in Section 8.3.14.8.

This command uses the PMBus® read or write byte protocol.

The details of this register are shown in Table 9-69.

Table 8-58 ADC_CONFIG_1 Register Description
BitName

Value

Description

Default

Access

7

EOC

End of conversion indication (Active Low)

Read

1

ADC is busy (Conversion in progress)

0

0

Conversion done

6

CONVST

Software conversion start control (used with MODE = 01)

Read/Write

1

Start conversion

0

0

Do not start conversion

5:4

MODE

ADC sampling mode

11

Continuous conversion - Single channel

00

10

Single channel single conversion - External pin controlled

01

Single channel single conversion – software controlled

00

Continuous conversion – auto sequenced

3:0

CONV_CH_SEL

Parameter/ADC Channel selection for sampling (MODE = 01 or 10 or 11)

1001-1111

Reserved

0000

1000

GND (Applicable only in MODE = 01 or 10)

0111

VIREF (Applicable only in MODE = 01 or 10)

0110

ADDR1 (Applicable only in MODE = 01 or 10)

0101

ADDR0 (Applicable only in MODE = 01 or 10)

0100

VAUX

0011

VTEMP

0010

IIN

0001

VOUT

0000

VIN

Note:
  • A write command to this register should be preceded by the MFR_WRITE_PROTECT command to unlock the device first to prevent accidental accidental/spurious writes.

  • MODE = 10 or 01 are debug-only modes and not recommended to be used during normal operation as they prevent the ADC from sampling all the necessary signals needed for the eFuse protection features.